Can the EcoFlow Delta Pro (Gen 1) Run a Full-Size 26 Cu. Ft. French Door Refrigerator?

Live runtime simulator, solar recharge calculator and NEC / IEC breaker & cable schematic for the EcoFlow Delta Pro (Gen 1) (3,600 Wh) paired with the Full-Size 26 Cu. Ft. French Door Refrigerator.

Configure your system

800 W
25 ft (7.6 m)
35%
Source outlets
NEMA TT-30R / 5-20R
Load connection
NEMA 5-15P
Verified Hardware Match

Check current bundle pricing for the EcoFlow Delta Pro (Gen 1) plus a transfer switch kit for this setup.

As an Amazon Associate, we earn from qualifying purchases.

Verified Compatible

EcoFlow Delta Pro (Gen 1) handles 160 W continuous and 1,100 W surge with headroom.

3,440 W of continuous capacity left for other circuits.

Continuous load
4%
Runtime (no sun)
54.6 hrs
35% duty · 85% inverter eff.
Solar recharge
5.6 hrs
1.3 sun-days at 800 W
Min. copper wire
14 AWG
0.2% drop @ 25 ft
Overcurrent device
15A Breaker
1.3A load × 1.25 = 1.7A
Live schematic & breaker sizing diagram 120V AC • NEC 125% Rule
SOLAR PV INPUT 800 W PV MC4 / XT60 · MPPT POWER SOURCE / INVERTER EcoFlow Delta Pro (Gen 1) 3,600 Wh • 3,600 W 7,200 W surge • 120V 4% load 15A OCPD 14 AWG Cu 1.3A @ 120V CONNECTED LOAD Full-Size 26 Cu. Ft. French Door Refrigera… 160 W running 1,100 W surge 120V load

Engineering report · reviewed against NEC 2026 & BS 7671:2018+A2

Engineering Breakdown: Running a Full-Size 26 Cu. Ft. French Door Refrigerator on the EcoFlow Delta Pro (Gen 1)

US/NA: Verified Compatible UK/EU/AU: Verified Compatible 4% inverter utilization

When pairing the EcoFlow Delta Pro (Gen 1) (3,600 Wh LiFePO4 capacity, 3,600 W continuous, 7,200 W surge) with a Full-Size 26 Cu. Ft. French Door Refrigerator (160 W running, 1,100 W starting surge), the system operates at 4% of continuous inverter capacity on a 120 V North American circuit and 4% on a 230 V UK/EU/AU circuit. At a 100% duty cycle and 85% inverter efficiency, a full battery delivers roughly 19.1 hrs of off-grid runtime. Wiring the connection over a 25 ft run calls for a 15 A breaker and 14 AWG copper, terminated at a NEMA 5-15P connection.

1. Compatibility Verdict & Inverter Load Utilization

In North American mode the Full-Size 26 Cu. Ft. French Door Refrigerator loads the EcoFlow Delta Pro (Gen 1)'s inverter to 4% of its 3,600 W continuous rating and 15% of its 7,200 W surge rating. Both figures are under the 80% sustained-load guideline, so this is a comfortable, verified match with 3,440 W of spare capacity for lights, a router or a refrigerator on the same unit.

CheckLoad requiresEcoFlow Delta Pro providesUS/NAUK/EU/AU
Continuous output 160 W 3,600 W Pass Pass
Start-up surge 1,100 W 7,200 W Pass Pass
Voltage 120 V / 230 V 120 V / 230 V Pass Pass
Connection NEMA 5-15P NEMA TT-30R / 5-20R UK/EU/AU: BS 1363 13A / Schuko CEE 7/4 / AS/NZS 3112 10A

Compressor appliances such as refrigerators and freezers draw very little on average — 160 W while running — but need 1,100 W for a moment each time the compressor kicks on. Their duty cycle is typically 30–40%, which is why a modest battery can keep food safe for a long time. The EcoFlow Delta Pro (Gen 1)'s 7,200 W surge rating comfortably handles each restart.

As a portable power station, the EcoFlow Delta Pro (Gen 1) integrates the LiFePO4 battery, inverter, MPPT solar controller and AC outlets in one chassis, so it can be wheeled to the load or connected to a transfer switch through its NEMA TT-30R / 5-20R outlet.

2. Real-World Runtime by Duty Cycle

Nameplate capacity is not usable capacity. DC-to-AC conversion, battery management overhead and cell protection reduce the 3,600 Wh rating to about 3,060 Wh of deliverable AC energy (85% system efficiency). Duty cycle is the share of each hour the load actually draws its running power — thermostats, pressure switches and intermittent use all lower it.

Runtime (h) = (3,600 Wh × 0.85) ÷ (160 W × duty cycle)
Duty cycleAverage drawRuntime (no solar)Energy per 24 h
25% 40 W 3.2 days 1.0 kWh
50% 80 W 38.3 hrs 1.9 kWh
65% 104 W 29.4 hrs 2.5 kWh
100% 160 W 19.1 hrs 3.8 kWh

At a 50% duty cycle the EcoFlow Delta Pro (Gen 1) covers a full day (38.3 hrs) without any recharge — ample for a typical overnight outage.

3. NEC 125% Breaker & Copper Wire Gauge Sizing

NEC 210.19(A) and 210.20(A) require conductors and overcurrent devices for continuous loads — anything running three hours or more, which includes EV charging and HVAC — to be rated at 125% of the load current. For this pairing: 160 W ÷ 120 V = 1.3 A, × 1.25 = 1.7 A, which rounds up to the next standard NEC 240.6 size of 15 A. The conductor must be protected by that breaker (75 °C ampacity at least 15 A) and keep round-trip voltage drop at or below 3%, so longer runs are upsized.

Breaker ≥ (160 W ÷ 120 V) × 1.25 = 1.7 A → 15 A
Voltage drop % = (2 × L × I × R) ÷ V × 100

North America (NEC, THHN copper, 75 °C)

One-way distanceBreakerMin. copperVoltage dropNote
25 ft (7.6 m) 15 A 14 AWG 0.17% Sized by ampacity
50 ft (15.2 m) 15 A 14 AWG 0.34% Sized by ampacity
75 ft (22.9 m) 15 A 14 AWG 0.51% Sized by ampacity
100 ft (30.5 m) 15 A 14 AWG 0.68% Sized by ampacity

UK / EU / Australia (IEC 60364 / BS 7671, PVC copper, method C)

IEC-based codes size protection by design current rather than a blanket 125% multiplier: Ib ≤ In ≤ Iz. At 230 V the load draws 0.7 A, so a 6 A Type B/C MCB with RCD protection applies. In the UK, BS 7671 Section 722 additionally requires a dedicated circuit and Type A or Type B RCD for EV charge points.

One-way distanceMCBMin. cableVoltage drop
7.5 m (25 ft) 6 A 1.5 mm² 0.05%
15 m (49 ft) 6 A 1.5 mm² 0.11%
22.5 m (74 ft) 6 A 1.5 mm² 0.16%
30 m (98 ft) 6 A 1.5 mm² 0.22%

Because the current is modest, 14 AWG copper stays within the voltage-drop target all the way to 100 ft.

4. Solar Array Recharge Time Breakdown

The EcoFlow Delta Pro (Gen 1) accepts up to 1,600 W of photovoltaic input. Real arrays rarely deliver nameplate output, so we apply an 80% harvest factor for MPPT conversion, cell temperature and soiling, and convert hours to days using 4.5 peak-sun-hours — a conservative annual average for the US, southern Europe and Australia (UK winters can fall below 1.5).

PV arrayReal harvest0–100% rechargeSun-days @ 4.5 PSHNet with load @ 50%
400 W 320 W 11.3 hrs 2.5 +240 W
800 W 640 W 5.6 hrs 1.3 +560 W
1,600 W 1,280 W 2.8 hrs 0.6 +1,200 W

A typical 800 W portable array refills the battery in about 5.6 hrs of strong sun, while maxing out the 1,600 W input cuts that to 2.8 hrs. To fully offset the Full-Size 26 Cu. Ft. French Door Refrigerator at a 50% duty cycle (80 W average) during daylight you need roughly 100 W of panels, which this unit can accept.

5. Frequently Asked Questions

Can the EcoFlow Delta Pro (Gen 1) run a Full-Size 26 Cu. Ft. French Door Refrigerator?

Yes. The EcoFlow Delta Pro (Gen 1) delivers 3,600 W continuous and 7,200 W surge, covering the Full-Size 26 Cu. Ft. French Door Refrigerator's 160 W running and 1,100 W start-up draw at 4% inverter utilization.

How long will the EcoFlow Delta Pro (Gen 1) run a Full-Size 26 Cu. Ft. French Door Refrigerator?

With 3,600 Wh of capacity and 85% inverter efficiency, expect about 19.1 hrs of continuous operation and 38.3 hrs at a 50% duty cycle. Adding solar input during the day extends this further.

What breaker and wire size do I need to connect a Full-Size 26 Cu. Ft. French Door Refrigerator to the EcoFlow Delta Pro (Gen 1)?

In the US, 160 W at 120 V is 1.3 A; applying the NEC 125% continuous-load rule gives 1.7 A, so use a 15 A breaker and 14 AWG copper for runs up to 25 ft (0.2% voltage drop). In 230 V markets the load draws 0.7 A, protected by a 6 A MCB on 1.5 mm² cable for runs up to 7.5 m. Receptacle: NEMA 5-15P (US) or BS 1363 13A / Schuko CEE 7/4 / AS/NZS 3112 10A (UK/EU/AU).

How long does it take to recharge the EcoFlow Delta Pro (Gen 1) with solar panels?

With an 800 W array and an 80% real-world harvest factor, a full recharge takes about 5.6 hrs of peak sun (1.3 days at 4.5 peak-sun-hours). At its maximum 1,600 W solar input it drops to 2.8 hrs.

Methodology & safety note

Specifications come from manufacturer datasheets in our open dataset; ampacity and resistance values follow NEC Table 310.16 and Chapter 9 Table 8, and BS 7671 Appendix 4. Calculations assume copper conductors, 30 °C ambient and no bundling derating. Inverter-to-panel connections require a listed transfer switch or interlock to prevent back-feeding the grid. These results are an engineering estimate, not a substitute for a licensed electrician and local permit. See our methodology and safety disclaimer.

Status dots show the North American verdict: compatible, conditional, not compatible.

Other loads on the EcoFlow Delta Pro (Gen 1)

All 50 loads on the EcoFlow Delta Pro (Gen 1) →

Other power stations for the Full-Size 26 Cu. Ft. French Door Refrigerator

Compare every source for this load →

More Kitchen & Home Appliances on the EcoFlow Delta Pro (Gen 1)