Can the EcoFlow Delta Pro (Gen 1) Run a Chevy Equinox EV (Level 1 120V / 12A Cord)?

Live runtime simulator, solar recharge calculator and NEC / IEC breaker & cable schematic for the EcoFlow Delta Pro (Gen 1) (3,600 Wh) paired with the Chevy Equinox EV (Level 1 120V / 12A Cord).

Configure your system

800 W
25 ft (7.6 m)
100%
Source outlets
NEMA TT-30R / 5-20R
Load connection
NEMA 5-15P
EV range rate
≈ 5 mi (7 km) of range per hour of charging
Verified Hardware Match

Check current bundle pricing for the EcoFlow Delta Pro (Gen 1) plus a transfer switch kit for this setup.

As an Amazon Associate, we earn from qualifying purchases.

Verified Compatible

EcoFlow Delta Pro (Gen 1) handles 1,440 W continuous and 1,440 W surge with headroom.

2,160 W of continuous capacity left for other circuits.

Continuous load
40%
Runtime (no sun)
2.1 hrs
100% duty · 85% inverter eff.
Solar recharge
5.6 hrs
1.3 sun-days at 800 W
Min. copper wire
14 AWG
1.5% drop @ 25 ft
Overcurrent device
15A Breaker
12.0A load × 1.25 = 15.0A
Live schematic & breaker sizing diagram 120V AC • NEC 125% Rule
SOLAR PV INPUT 800 W PV MC4 / XT60 · MPPT POWER SOURCE / INVERTER EcoFlow Delta Pro (Gen 1) 3,600 Wh • 3,600 W 7,200 W surge • 120V 40% load 15A OCPD 14 AWG Cu 12.0A @ 120V CONNECTED LOAD Chevy Equinox EV (Level 1 120V / 12A C… 1,440 W running 1,440 W surge 120V load

Engineering report · reviewed against NEC 2026 & BS 7671:2018+A2

Engineering Breakdown: Running a Chevy Equinox EV (Level 1 120V / 12A Cord) on the EcoFlow Delta Pro (Gen 1)

US/NA: Verified Compatible UK/EU/AU: Verified Compatible 40% inverter utilization

When pairing the EcoFlow Delta Pro (Gen 1) (3,600 Wh LiFePO4 capacity, 3,600 W continuous, 7,200 W surge) with a Chevy Equinox EV (Level 1 120V / 12A Cord) (1,440 W running, 1,440 W starting surge), the system operates at 40% of continuous inverter capacity on a 120 V North American circuit and 77% on a 230 V UK/EU/AU circuit. At a 100% duty cycle and 85% inverter efficiency, a full battery delivers roughly 2.1 hrs of off-grid runtime. Wiring the connection over a 25 ft run calls for a 15 A breaker and 14 AWG copper, terminated at a NEMA 5-15P connection.

1. Compatibility Verdict & Inverter Load Utilization

In North American mode the Chevy Equinox EV (Level 1 120V / 12A Cord) loads the EcoFlow Delta Pro (Gen 1)'s inverter to 40% of its 3,600 W continuous rating and 20% of its 7,200 W surge rating. Both figures are under the 80% sustained-load guideline, so this is a comfortable, verified match with 2,160 W of spare capacity for lights, a router or a refrigerator on the same unit.

CheckLoad requiresEcoFlow Delta Pro providesUS/NAUK/EU/AU
Continuous output 1,440 W (2,760 W @ 230V) 3,600 W Pass Pass
Start-up surge 1,440 W 7,200 W Pass Pass
Voltage 120 V / 230 V 120 V / 230 V Pass Pass
Connection NEMA 5-15P NEMA TT-30R / 5-20R UK/EU/AU: Type 2 EVSE · IEC 60309 16A Commando

An EVSE is a constant-current device: the vehicle draws exactly the current advertised by the J1772/NACS pilot signal, so the 1,440 W figure is both the running load and the start-up load — there is no motor inrush. That makes the calculation unusually clean. If you want to stay under the 80% sustained-load guideline, set the charge current in the vehicle app to 24 A or less, which keeps the EcoFlow Delta Pro (Gen 1) at roughly 2,880 W. A full battery delivers about 2.8 kWh into the pack after inverter and on-board charger losses, worth roughly 10 miles (16 km) of driving at 3.5 mi/kWh.

As a portable power station, the EcoFlow Delta Pro (Gen 1) integrates the LiFePO4 battery, inverter, MPPT solar controller and AC outlets in one chassis, so it can be wheeled to the load or connected to a transfer switch through its NEMA TT-30R / 5-20R outlet.

2. Real-World Runtime by Duty Cycle

Nameplate capacity is not usable capacity. DC-to-AC conversion, battery management overhead and cell protection reduce the 3,600 Wh rating to about 3,060 Wh of deliverable AC energy (85% system efficiency). EV charging runs at a fixed current, so the 100% row is the realistic figure; lower rows apply only if you schedule charging in intervals.

Runtime (h) = (3,600 Wh × 0.85) ÷ (1,440 W × duty cycle)
Duty cycleAverage drawRuntime (no solar)Energy per 24 h
25% 360 W 8.5 hrs 8.6 kWh
50% 720 W 4.3 hrs 17.3 kWh
65% 936 W 3.3 hrs 22.5 kWh
100% 1,440 W 2.1 hrs 34.6 kWh

Even at a 50% duty cycle the battery lasts 4.3 hrs, so plan on solar, grid or generator recharging for anything longer than an evening outage.

3. NEC 125% Breaker & Copper Wire Gauge Sizing

NEC 210.19(A) and 210.20(A) require conductors and overcurrent devices for continuous loads — anything running three hours or more, which includes EV charging and HVAC — to be rated at 125% of the load current. For this pairing: 1,440 W ÷ 120 V = 12.0 A, × 1.25 = 15.0 A, which rounds up to the next standard NEC 240.6 size of 15 A. The conductor must be protected by that breaker (75 °C ampacity at least 15 A) and keep round-trip voltage drop at or below 3%, so longer runs are upsized.

Breaker ≥ (1,440 W ÷ 120 V) × 1.25 = 15.0 A → 15 A
Voltage drop % = (2 × L × I × R) ÷ V × 100

North America (NEC, THHN copper, 75 °C)

One-way distanceBreakerMin. copperVoltage dropNote
25 ft (7.6 m) 15 A 14 AWG 1.53% Sized by ampacity
50 ft (15.2 m) 15 A 12 AWG 1.93% Upsized for voltage drop
75 ft (22.9 m) 15 A 12 AWG 2.89% Upsized for voltage drop
100 ft (30.5 m) 15 A 10 AWG 2.42% Upsized for voltage drop

UK / EU / Australia (IEC 60364 / BS 7671, PVC copper, method C)

IEC-based codes size protection by design current rather than a blanket 125% multiplier: Ib ≤ In ≤ Iz. At 230 V the load draws 12.0 A (the EVSE's 12 A pilot current at 230 V), so a 13 A Type B/C MCB with RCD protection applies. In the UK, BS 7671 Section 722 additionally requires a dedicated circuit and Type A or Type B RCD for EV charge points.

One-way distanceMCBMin. cableVoltage drop
7.5 m (25 ft) 13 A 1.5 mm² 0.95%
15 m (49 ft) 13 A 1.5 mm² 1.89%
22.5 m (74 ft) 13 A 1.5 mm² 2.84%
30 m (98 ft) 13 A 2.5 mm² 2.32%

Moving the EcoFlow Delta Pro (Gen 1) from 25 ft to 100 ft away forces the conductor up from 14 AWG to 10 AWG — park the unit as close to the load as ventilation and weather protection allow.

4. Solar Array Recharge Time Breakdown

The EcoFlow Delta Pro (Gen 1) accepts up to 1,600 W of photovoltaic input. Real arrays rarely deliver nameplate output, so we apply an 80% harvest factor for MPPT conversion, cell temperature and soiling, and convert hours to days using 4.5 peak-sun-hours — a conservative annual average for the US, southern Europe and Australia (UK winters can fall below 1.5).

PV arrayReal harvest0–100% rechargeSun-days @ 4.5 PSHNet with load @ 50%
400 W 320 W 11.3 hrs 2.5 −400 W
800 W 640 W 5.6 hrs 1.3 −80 W
1,600 W 1,280 W 2.8 hrs 0.6 +560 W

A typical 800 W portable array refills the battery in about 5.6 hrs of strong sun, while maxing out the 1,600 W input cuts that to 2.8 hrs. To fully offset the Chevy Equinox EV (Level 1 120V / 12A Cord) at a 50% duty cycle (720 W average) during daylight you need roughly 900 W of panels, which this unit can accept.

5. Frequently Asked Questions

Can the EcoFlow Delta Pro (Gen 1) run a Chevy Equinox EV (Level 1 120V / 12A Cord)?

Yes. The EcoFlow Delta Pro (Gen 1) delivers 3,600 W continuous and 7,200 W surge, covering the Chevy Equinox EV (Level 1 120V / 12A Cord)'s 1,440 W running and 1,440 W start-up draw at 40% inverter utilization.

How many miles of range can the EcoFlow Delta Pro (Gen 1) add to a Chevy Equinox EV?

A full 3,600 Wh charge delivers about 2.8 kWh to the vehicle battery after inverter (85%) and on-board charger (90%) losses — roughly 10 miles at 3.5 mi/kWh. At the full 1,440 W charge rate that takes 2.1 hrs.

What breaker and wire size do I need to connect a Chevy Equinox EV (Level 1 120V / 12A Cord) to the EcoFlow Delta Pro (Gen 1)?

In the US, 1,440 W at 120 V is 12.0 A; applying the NEC 125% continuous-load rule gives 15.0 A, so use a 15 A breaker and 14 AWG copper for runs up to 25 ft (1.5% voltage drop). In 230 V markets the load draws 12.0 A, protected by a 13 A MCB on 1.5 mm² cable for runs up to 7.5 m. Receptacle: NEMA 5-15P (US) or Type 2 EVSE · IEC 60309 16A Commando (UK/EU/AU).

How long does it take to recharge the EcoFlow Delta Pro (Gen 1) with solar panels?

With an 800 W array and an 80% real-world harvest factor, a full recharge takes about 5.6 hrs of peak sun (1.3 days at 4.5 peak-sun-hours). At its maximum 1,600 W solar input it drops to 2.8 hrs.

Methodology & safety note

Specifications come from manufacturer datasheets in our open dataset; ampacity and resistance values follow NEC Table 310.16 and Chapter 9 Table 8, and BS 7671 Appendix 4. Calculations assume copper conductors, 30 °C ambient and no bundling derating. Inverter-to-panel connections require a listed transfer switch or interlock to prevent back-feeding the grid. These results are an engineering estimate, not a substitute for a licensed electrician and local permit. See our methodology and safety disclaimer.

Status dots show the North American verdict: compatible, conditional, not compatible.

Other loads on the EcoFlow Delta Pro (Gen 1)

All 50 loads on the EcoFlow Delta Pro (Gen 1) →

Other power stations for the Chevy Equinox EV (Level 1 120V / 12A Cord)

Compare every source for this load →

More Electric Vehicle Charging on the EcoFlow Delta Pro (Gen 1)