Can the Anker SOLIX F3800 Plus Run a 1.0 HP Deep Well Submersible Pump (240V)?

Live runtime simulator, solar recharge calculator and NEC / IEC breaker & cable schematic for the Anker SOLIX F3800 Plus (3,840 Wh) paired with the 1.0 HP Deep Well Submersible Pump (240V).

Configure your system

800 W
25 ft (7.6 m)
30%
Source outlets
NEMA 14-50R / L14-30R / TT-30R
Load connection
NEMA L14-30P / Hardwired
Verified Hardware Match

Check current bundle pricing for the Anker SOLIX F3800 Plus plus a transfer switch kit for this setup.

As an Amazon Associate, we earn from qualifying purchases.

Verified Compatible

Anker SOLIX F3800 Plus handles 1,650 W continuous and 4,500 W surge with headroom.

4,350 W of continuous capacity left for other circuits.

Continuous load
28%
Runtime (no sun)
6.6 hrs
30% duty · 85% inverter eff.
Solar recharge
6.0 hrs
1.3 sun-days at 800 W
Min. copper wire
14 AWG
0.4% drop @ 25 ft
Overcurrent device
15A Breaker
6.9A load × 1.25 = 8.6A
Live schematic & breaker sizing diagram 120/240V Split-Phase • NEC 125% Rule
SOLAR PV INPUT 800 W PV MC4 / XT60 · MPPT POWER SOURCE / INVERTER Anker SOLIX F3800 Plus 3,840 Wh • 6,000 W 9,000 W surge • 120/240V 28% load 15A OCPD 14 AWG Cu 6.9A @ 240V CONNECTED LOAD 1.0 HP Deep Well Submersible Pump (240… 1,650 W running 4,500 W surge 240V load

Engineering report · reviewed against NEC 2026 & BS 7671:2018+A2

Engineering Breakdown: Running a 1.0 HP Deep Well Submersible Pump (240V) on the Anker SOLIX F3800 Plus

US/NA: Verified Compatible UK/EU/AU: Verified Compatible 28% inverter utilization

When pairing the Anker SOLIX F3800 Plus (3,840 Wh LiFePO4 capacity, 6,000 W continuous, 9,000 W surge) with a 1.0 HP Deep Well Submersible Pump (240V) (1,650 W running, 4,500 W starting surge), the system operates at 28% of continuous inverter capacity on a 240 V North American circuit and 28% on a 230 V UK/EU/AU circuit. At a 100% duty cycle and 85% inverter efficiency, a full battery delivers roughly 2.0 hrs of off-grid runtime. Wiring the connection over a 25 ft run calls for a 15 A breaker and 14 AWG copper, terminated at a NEMA L14-30P / Hardwired connection.

1. Compatibility Verdict & Inverter Load Utilization

In North American mode the 1.0 HP Deep Well Submersible Pump (240V) loads the Anker SOLIX F3800 Plus's inverter to 28% of its 6,000 W continuous rating and 50% of its 9,000 W surge rating. Both figures are under the 80% sustained-load guideline, so this is a comfortable, verified match with 4,350 W of spare capacity for lights, a router or a refrigerator on the same unit.

CheckLoad requiresAnker SOLIX F3800 Plus providesUS/NAUK/EU/AU
Continuous output 1,650 W 6,000 W Pass Pass
Start-up surge 4,500 W 9,000 W Pass Pass
Voltage 240 V / 230 V 120/240 V / 230 V Pass Pass
Connection NEMA L14-30P / Hardwired NEMA 14-50R / L14-30R / TT-30R UK/EU/AU: Hardwired via DP isolator · IEC 60309 32A

Pumps are short-cycling, high-inrush loads. A well or sump pump might run for only 1–3 minutes at a time, but every start pulls 4,500 W — 2.7× its 1,650 W running draw — as the motor accelerates a column of water. That is why a pump that "only uses 1,650 W" still trips undersized inverters. Deep-well submersibles in North America are almost always 240 V two-wire or three-wire motors, so a 120 V-only station cannot drive them without a step-up transformer. A larger pressure tank reduces the number of starts per hour and is a worthwhile upgrade for off-grid systems built around the Anker SOLIX F3800 Plus.

As a portable power station, the Anker SOLIX F3800 Plus integrates the LiFePO4 battery, inverter, MPPT solar controller and AC outlets in one chassis, so it can be wheeled to the load or connected to a transfer switch through its NEMA 14-50R / L14-30R / TT-30R outlet.

2. Real-World Runtime by Duty Cycle

Nameplate capacity is not usable capacity. DC-to-AC conversion, battery management overhead and cell protection reduce the 3,840 Wh rating to about 3,264 Wh of deliverable AC energy (85% system efficiency). Duty cycle is the share of each hour the load actually draws its running power — thermostats, pressure switches and intermittent use all lower it.

Runtime (h) = (3,840 Wh × 0.85) ÷ (1,650 W × duty cycle)
Duty cycleAverage drawRuntime (no solar)Energy per 24 h
25% 413 W 7.9 hrs 9.9 kWh
50% 825 W 4.0 hrs 19.8 kWh
65% 1,073 W 3.0 hrs 25.7 kWh
100% 1,650 W 2.0 hrs 39.6 kWh

Even at a 50% duty cycle the battery lasts 4.0 hrs, so plan on solar, grid or generator recharging for anything longer than an evening outage.

3. NEC 125% Breaker & Copper Wire Gauge Sizing

NEC 210.19(A) and 210.20(A) require conductors and overcurrent devices for continuous loads — anything running three hours or more, which includes EV charging and HVAC — to be rated at 125% of the load current. For this pairing: 1,650 W ÷ 240 V = 6.9 A, × 1.25 = 8.6 A, which rounds up to the next standard NEC 240.6 size of 15 A. The conductor must be protected by that breaker (75 °C ampacity at least 15 A) and keep round-trip voltage drop at or below 3%, so longer runs are upsized.

Breaker ≥ (1,650 W ÷ 240 V) × 1.25 = 8.6 A → 15 A
Voltage drop % = (2 × L × I × R) ÷ V × 100

North America (NEC, THHN copper, 75 °C)

One-way distanceBreakerMin. copperVoltage dropNote
25 ft (7.6 m) 15 A 14 AWG 0.44% Sized by ampacity
50 ft (15.2 m) 15 A 14 AWG 0.88% Sized by ampacity
75 ft (22.9 m) 15 A 14 AWG 1.32% Sized by ampacity
100 ft (30.5 m) 15 A 14 AWG 1.76% Sized by ampacity

UK / EU / Australia (IEC 60364 / BS 7671, PVC copper, method C)

IEC-based codes size protection by design current rather than a blanket 125% multiplier: Ib ≤ In ≤ Iz. At 230 V the load draws 7.2 A, so a 10 A Type B/C MCB with RCD protection applies. In the UK, BS 7671 Section 722 additionally requires a dedicated circuit and Type A or Type B RCD for EV charge points.

One-way distanceMCBMin. cableVoltage drop
7.5 m (25 ft) 10 A 1.5 mm² 0.57%
15 m (49 ft) 10 A 1.5 mm² 1.13%
22.5 m (74 ft) 10 A 1.5 mm² 1.70%
30 m (98 ft) 10 A 1.5 mm² 2.26%

Because the current is modest, 14 AWG copper stays within the voltage-drop target all the way to 100 ft.

4. Solar Array Recharge Time Breakdown

The Anker SOLIX F3800 Plus accepts up to 3,200 W of photovoltaic input. Real arrays rarely deliver nameplate output, so we apply an 80% harvest factor for MPPT conversion, cell temperature and soiling, and convert hours to days using 4.5 peak-sun-hours — a conservative annual average for the US, southern Europe and Australia (UK winters can fall below 1.5).

PV arrayReal harvest0–100% rechargeSun-days @ 4.5 PSHNet with load @ 50%
400 W 320 W 12.0 hrs 2.7 −505 W
800 W 640 W 6.0 hrs 1.3 −185 W
1,600 W 1,280 W 3.0 hrs 0.7 +455 W
3,000 W 2,400 W 1.6 hrs 0.4 +1,575 W
3,200 W 2,560 W 1.5 hrs 0.3 +1,735 W

A typical 800 W portable array refills the battery in about 6.0 hrs of strong sun, while maxing out the 3,200 W input cuts that to 1.5 hrs. To fully offset the 1.0 HP Deep Well Submersible Pump (240V) at a 50% duty cycle (825 W average) during daylight you need roughly 1,050 W of panels, which this unit can accept.

5. Frequently Asked Questions

Can the Anker SOLIX F3800 Plus run a 1.0 HP Deep Well Submersible Pump (240V)?

Yes. The Anker SOLIX F3800 Plus delivers 6,000 W continuous and 9,000 W surge, covering the 1.0 HP Deep Well Submersible Pump (240V)'s 1,650 W running and 4,500 W start-up draw at 28% inverter utilization.

How long will the Anker SOLIX F3800 Plus run a 1.0 HP Deep Well Submersible Pump (240V)?

With 3,840 Wh of capacity and 85% inverter efficiency, expect about 2.0 hrs of continuous operation and 4.0 hrs at a 50% duty cycle. Adding solar input during the day extends this further.

What breaker and wire size do I need to connect a 1.0 HP Deep Well Submersible Pump (240V) to the Anker SOLIX F3800 Plus?

In the US, 1,650 W at 240 V is 6.9 A; applying the NEC 125% continuous-load rule gives 8.6 A, so use a 15 A breaker and 14 AWG copper for runs up to 25 ft (0.4% voltage drop). In 230 V markets the load draws 7.2 A, protected by a 10 A MCB on 1.5 mm² cable for runs up to 7.5 m. Receptacle: NEMA L14-30P / Hardwired (US) or Hardwired via DP isolator · IEC 60309 32A (UK/EU/AU).

How long does it take to recharge the Anker SOLIX F3800 Plus with solar panels?

With an 800 W array and an 80% real-world harvest factor, a full recharge takes about 6.0 hrs of peak sun (1.3 days at 4.5 peak-sun-hours). At its maximum 3,200 W solar input it drops to 1.5 hrs.

Methodology & safety note

Specifications come from manufacturer datasheets in our open dataset; ampacity and resistance values follow NEC Table 310.16 and Chapter 9 Table 8, and BS 7671 Appendix 4. Calculations assume copper conductors, 30 °C ambient and no bundling derating. Inverter-to-panel connections require a listed transfer switch or interlock to prevent back-feeding the grid. These results are an engineering estimate, not a substitute for a licensed electrician and local permit. See our methodology and safety disclaimer.

Status dots show the North American verdict: compatible, conditional, not compatible.

Other loads on the Anker SOLIX F3800 Plus

All 50 loads on the Anker SOLIX F3800 Plus →

Other power stations for the 1.0 HP Deep Well Submersible Pump (240V)

Compare every source for this load →

More Pumps & Water Systems on the Anker SOLIX F3800 Plus